Product series | TeSys |
---|---|
Product series | TeSys Deca |
product type | Contactor |
Product short name | LC1D |
Application fields of contactors | Applied to AC loads with a power factor greater than or equal to 0.95 Applied to non inductive or micro inductive loads, resistance furnaces |
Utilization category | AC-3 AC-3e AC-4 AC-1 |
number | 3P |
Rated working voltage [Ue] | Power circuit:<=300 V DC 25… 400 Hz Power circuit:<=690 V AC |
Rated working current [Ie] | 125 A (when operating temperature<=60 ° C) When operating voltage<=<=1000 V AC AC-1 for power circuit 80 A (when operating temperature<=60 ° C) When operating voltage<=<=440 V AC AC-3 for power circuit 80 A (when operating temperature<=60 ° C) and operating voltage<=<=440 V AC-3e for power circuit |
[Uc] control circuit voltage | 48 V DC |
Electric motor power (kW) | 22 kW when operating voltage<=220… 230 V AC 50/60 Hz (AC-3) 37 kW when operating voltage<=380… 400 V AC 50/60 Hz (AC-3) 45 kW when operating voltage<=415… 440 V AC 50/60 Hz (AC-3) 55 kW when operating voltage<=500 V AC 50/60 Hz (AC-3) 45 kW when operating voltage<=660… 690 V AC 50/60 Hz (AC-3) 15 kW when operating voltage<=400 V AC 50/60 Hz (AC-4) 22 kW when operating voltage<=220… 230 V AC 50/60 Hz (AC-3e) 37 kW when operating voltage<=380… 400 V AC 50/60 Hz (AC-3e) 45 kW when operating voltage<=415… 440 V AC 50/60 Hz (AC-3e) 55 kW when operating voltage<=500 V AC 50/60 Hz (AC-3e) 45 kW when operating voltage<=660… 690 V AC 50/60 Hz (AC-3e) |
---|---|
Motor Power | 7.5 hp for 1-phase motors when operating voltage<=120 V AC 50/60 Hz 15 hp when operating voltage<=230/240 V AC 50/60 Hz for 1-phase motors 30 hp for 3-phase motors when operating voltage<=200/208 V AC 50/60 Hz 30 hp for 3-phase motors when operating voltage<=230/240 V AC 50/60 Hz 60 hp for 3-phase motors when operating voltage<=460/480 V AC 50/60 Hz 60 hp for 3-phase motors when operating voltage<=575/600 V AC 50/60 Hz |
model | LC1D |
Type of circuit contact | 3 NO |
Protective cover | have |
Agreed heating current [Ith] | 10 A (when operating temperature<=60 ° C) for signal circuit 125 A (when operating temperature<=60 ° C) for power circuit |
Rated connection capacity [Irms] | 140 A AC complies with IEC 60947-5-1 for signal circuits 250 A DC complies with IEC 60947-5-1 for signal circuits When the operating voltage is less than or equal to 440 V at 1100 A, the power circuit complies with IEC 60947 |
Rated breaking capacity | When the operating voltage is less than or equal to 440 V at 1100 A, the power circuit complies with IEC 60947 |
Rated short-time withstand current [Icw] | 640 A can last for 10 seconds when operating temperature<=40 ° C for power circuit 990 A can last for 1 second when operating temperature<=40 ° C for power circuit 135 A can last for 10 minutes when the operating temperature is<=40 ° C for the power circuit 320 A can last for 1 minute when the operating temperature is<=40 ° C for the power circuit 100 A can last for 1 second for signal circuits 120 A can last for 500 ms for signal circuits 140 A can sustain 100 ms for signal circuits |
Fuses used in conjunction with relays | 10 A gG, For signal circuits that comply with IEC 60947-5-1 200 A gG when operating voltage<=<=690 V with Type 1, for power circuit 160 A gG when operating voltage<=<=690 V in combination with Type 2, for power circuit |
Average impedance | 0.8 m Ω – It 125 A 50 Hz for power circuit |
Power consumption per pole | 5.1 W AC-3 12.5 W AC-1 5.1 W AC-3e |
Rated insulation voltage [Ui] | Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Power circuit: 1000 V in accordance with IEC 60947-4-1 Signal circuit: 690 V in accordance with IEC 60947-1 Signal circuit: 600 V CSA certified Signal circuit: 600 V UL certified |
overvoltage category | III |
pollution degree | 3 |
Rated impulse withstand voltage [Uimp] | 8 kV complies with IEC 60947 |
Safety and reliability level | B10d=1369863 nominal load contactors comply with EN/ISO 13849-1 The contactor with B10d=20000000 mechanical loads complies with EN/ISO 13849-1 |
mechanical life | 4 Mcycles |
Electrical life | 0.8 Mcycles 125 A AC-1 U under conditions <= 440 V 1.5 Mcycles 80 A AC-3 U under conditions <= 440 V 1.5 Mcycles 80 A under AC-3e Ue conditions <= 440 V |
Control circuit characteristics | DC standard |
Surge suppression module | No built-in surge suppression module |
Control voltage limit | 0.1… 0.3 Uc (-40… 70 ° C): Coil releases DC 0.85… 1.1 Uc (-40… 55 ° C): Coil starting DC 1… 1.1 Uc (55… 70 ° C): Coil starting DC |
Surge power (W) | 22 W 20 °C) |
Absorption power consumption (W) | 22 W at… 20 ° C |
Action time | 95… 130 ms closed 20… 35 ms interruption |
time constant | 75 ms |
Maximum Operating Frequency | 3600 times/hour at 60 ° C |
Wiring ability | Control Circuit: Bolt Tightening 2 1… 2.5 mm ² Cable Type: Flexible Wire with Terminal Blocks Control Circuit: Bolt Tightening 1… 2.5 mm ² Cable Type: Flexible Wire with Terminal Blocks Control Circuit: Bolt Tightening 1… 4 mm ² Cable Type: Flexible Wire without Terminal Blocks Control Circuit: Bolt Tightening 2 1… 4 mm ² Cable Type: Flexible Wire without Terminal Blocks Control Circuit: Bolt Tightening 1… 4 mm ² Cable Type: Hardwire without Terminal Blocks Control Circuit: Bolt Tightening 2 1… 4 mm ² Cable Type: Hardwire without Terminal Blocks Power circuit: Terminal 1 4… 50 mm ² Cable type: Flexible wire without terminal block Power circuit: Terminal 2 4… 25 mm ² Cable type: Flexible cord without terminal block Power circuit: Terminal 1 4… 50 mm ² Cable type: Flexible wire with terminal block Power circuit: Terminal 2 4… 16 mm ² Cable type: Flexible wire with terminal block Power circuit: Terminal 1 4… 50 mm ² Cable type: Hardwire without terminal block Power circuit: Terminal 2 4… 25 mm ² Cable type: Hardwire without terminal block |
Tightening torque | Control circuit: 1.2 N.m fastened by bolts with a screwdriver Ø 6 flat mouth Control circuit: 1.2 N.m fastened with a screwdriver No. 2 cross screw using bolts Power circuit: 12 N.m through the terminal using a screwdriver Ø 6- Ø 8 flat mouth Power circuit: 12 N.m through terminal hexagonal 4 mm Control circuit: 1.2 N.m fastened with bolts using a screwdriver pozidriv No 2 |
Auxiliary contact type | 1 NO + 1 NC |
Auxiliary contact type | Type mechanical connection 1 NO+1 NC in accordance with IEC 60947-5-1 The type is mirrored with the main contact state. NC complies with IEC 60947-4-1 |
Signal loop frequency | 25…400 Hz |
Minimum switch voltage | 17 V for signal circuit |
Minimum switch current [Imin] | 5 mA for signal circuit |
insulation resistance | >10 M Ω for signal circuit |
Non overlapping time | 1.5 ms power loss between NC and NO contacts 1.5 ms power supply between NC and NO contacts |
Installation method | Bottom plate installation DIN-Rail Mounting |
standard | EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 CSA C22.2 No 14 UL 60947-4-1 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ IEC 60335-1:Clause 30.2 |
---|---|
Product Certification | CCC UL CB Scheme CSA CE UKCA 海事 EAC |
IP protection level | IP20 front panel complies with IEC 60529 |
Protective measures | TH complies with IEC 60068-2-30 |
Climate tolerance | Compliant with IACS E10 for exposure to hot flashes |
ambient air temperature | -40…60 °C 60… 70 ° C with capacity reduction |
Working altitude | 0…3000 m |
Fire resistance and ability to withstand abnormal high temperatures | 850 ° C complies with IEC 60695-2-1 |
Flame retardant | V1 complies with UL 94 |
Anti impact and vibration performance | Seismic performance when the contact is open (2 gn (5… 300 Hz)) Impact resistance performance when the contact is opened (8 gn (11ms)) Seismic performance when the contact is closed (3 gn (5… 300 Hz)) Impact resistance performance when the contact is closed (10 gn (11ms)) |
height | 127 mm |
width | 85 mm |
depth | 186 mm |
Net weight | 2.59 kg |